Transformer Apparent-Power Sizing Calculator — result sheet
Estimate load VA, transformer input VA, primary and secondary currents, and an ideal turns ratio for an AC transformer scenario.
Inputs used
Results
Visual chart
Breakdown
Calculation steps
Returned data table
Formula and methodology
Formula: S_load = P/PF; S_input = S_load/η; I₁ = S_input/V₁; I₂ = S_load/V₂; V₁/V₂ = N₁/N₂.
Transformer selection begins with apparent power rather than real watts alone when the load has a power factor. This calculator keeps load VA, efficiency, currents, and the ideal voltage-to-turns relationship separate so a planning estimate is not mistaken for a complete transformer design.
This result follows the calculator's declared inputs, precision, validation boundaries, and model limits.
Input contract
- Load real power — W; minimum 1.0E-6; maximum 1000000000000
- Load power factor — PF; minimum 1.0E-6; maximum 1
- Transformer efficiency — %; minimum 0.0001; maximum 100
- Primary voltage — V; minimum 1.0E-6; maximum 10000000
- Secondary voltage — V; minimum 1.0E-6; maximum 10000000
- Primary turns — turns; minimum 1.0E-6; maximum 1000000000
Worked example
| Input | Value |
|---|---|
| Load real power | 1000 |
| Load power factor | 0.8 |
| Transformer efficiency | 95 |
| Primary voltage | 230 |
| Secondary voltage | 24 |
| Primary turns | 1000 |
A 1,000 W load at PF 0.8 is 1,250 VA; at 95% efficiency the estimated input is 1,315.789 VA, with about 5.7208 A primary current and 52.0833 A secondary current.
Assumptions and limits
- The load power factor is positive and no more than one; its sign or leading/lagging nature is not modeled.
- Efficiency is entered as a percentage and applied to apparent-power planning arithmetic.
- The turns relationship is ideal and assumes the entered primary and secondary voltages are compatible RMS AC values.
- Inrush, regulation, harmonics, temperature rise, insulation, short-circuit duty, conductor sizing, and electrical-code requirements are excluded.
Calculator note
Source and methodology
Use the official WorldCalculate methodology policy for the source, formula, precision, and boundary standards behind this calculator.