Heat-Exchanger Effectiveness from NTU Calculator — result sheet
Calculate counterflow heat-exchanger effectiveness from number of transfer units and heat-capacity ratio.
Inputs used
Results
Visual chart
Breakdown
Calculation steps
Returned data table
Formula and methodology
Formula: For counterflow Cr≠1, effectiveness=(1−e^(−NTU(1−Cr)))/(1−Cr×e^(−NTU(1−Cr))); for Cr=1, effectiveness=NTU/(1+NTU).
The standard counterflow NTU relation reports a dimensionless effectiveness without pretending to know exchanger fouling, leakage, or measured temperatures.
This result follows the calculator's declared inputs, precision, validation boundaries, and model limits.
Input contract
- Number of transfer units — minimum 0; maximum 1000
- Heat-capacity ratio Cr — minimum 0; maximum 1
Worked example
| Input | Value |
|---|---|
| Number of transfer units | 2 |
| Heat-capacity ratio Cr | 0.5 |
Effectiveness ≈0.7746.
Assumptions and limits
- NTU is nonnegative and the heat-capacity ratio is between zero and one.
- The counterflow arrangement and constant-property model apply.
- Fouling, phase change, axial conduction, leakage, maldistribution, and pressure drop are not modeled.
Calculator note
Source and methodology
Use the official WorldCalculate methodology policy for the source, formula, precision, and boundary standards behind this calculator.
Planning estimate, not financial, medical, legal, or professional advice. © WorldCalculate — reuse with attribution. Built and curated by Hassan ALRowaie.