Battery Size from Load and Runtime — result sheet
Estimate the battery energy and amp-hour capacity needed for a load, runtime, voltage, usable-depth limit, efficiency, and reserve.
Inputs used
Results
Visual chart
Breakdown
Calculation steps
Returned data table
Formula and methodology
Formula: Load energy = P·t; required nominal energy = load energy ÷ (usable fraction × efficiency) × (1 + reserve); amp-hours = watt-hours ÷ voltage.
Battery sizing starts with the energy the load needs, then accounts for the fraction of the nameplate capacity that can be used, conversion losses, and a visible planning reserve. The result is an estimate of nominal watt-hours and amp-hours, not a promise of field runtime.
This result follows the calculator's declared inputs, precision, validation boundaries, and model limits.
Input contract
- Load power — W; minimum 1.0E-6; maximum 1000000000
- Required runtime — h; minimum 1.0E-6; maximum 1000000
- Battery system voltage — V; minimum 1.0E-6; maximum 1000000
- Usable capacity fraction — %; minimum 1.0E-6; maximum 100
- Conversion efficiency — %; minimum 1.0E-6; maximum 100
- Planning reserve — %; minimum 0; maximum 1000
Worked example
| Input | Value |
|---|---|
| Load power | 100 |
| Required runtime | 8 |
| Battery system voltage | 12 |
| Usable capacity fraction | 80 |
| Conversion efficiency | 90 |
| Planning reserve | 10 |
An 800 Wh load requirement becomes about 1,222.22 Wh or 101.85 Ah at 12 V after the stated limits and 10% reserve.
Assumptions and limits
- Load power is constant for the stated runtime and the battery voltage is treated as a nominal operating voltage.
- Usable capacity and efficiency are entered as fractions of nameplate performance; actual capacity changes with discharge rate, temperature, age, chemistry, and cutoff voltage.
- The reserve is a planning multiplier only and does not replace manufacturer limits, protection settings, thermal design, or a battery-system safety review.